NETWORKABLE ANALOGUE ADDRESSABLE FIRE ALARM CONTROL PANEL XFP
AdvantagesFull compatibility with Apollo’s XP95/Discovery and Hochiki’s ESP protocols - The ability to interconnect up to eight XFP main panels (any variant) onto a two wire RS485 network. Alternatively, up to eight XFP repeaters can be connected to a non-networked XFP main panel
- Combined keypad / keyswitch entry to Access Levels 2 & 3
- Two independently programmable conventional sounder circuits
- Two programmable inputs
- A fault output relay and three programmable relay outputs with voltage free changeover contacts
- Three zone dependency functions (A, B & C to EN54-2 Clause 7.12) A day/night (building occupied/unoccupied) function
- An investigation delay period function
- Individual sensitivity settings for each device
- A phased evacuation and delays to outputs facility (to EN54-2 Clause 7.11)
- An alarm counter that records the number of times the panel has been in an alarm state (to EN54-2 Clause 7.13)
- Powerful short circuit protected loop drivers, capable of supporting up to 40 loop
- powered 10mA sounders per loop
- An integral EN54-4/A2 switch mode PSU rated @ 185-260V a.c. 50/60Hz (1.4A on a 16 zone panel, 3A on a 32 zone panel)
- Earth fault monitoring
- An easy to read, 80 character back-lit display
- 40 characters of custom text per device
- 999 event monitoring
- Comprehensive test facilities (to EN54-2 Clause 10) and a wide range of maintenance & commissioning functions including auto-learn loops, monitor a point, test outputs, one man walk test and loop continuity test
- An intuitive Windows based upload-download PC program that allows the system to be programmed quickly and easily
- Full compatibility with Context Plus’ Hush Button fire alarm solution for houses of multiple occupation
- Optional flush-mounting stainless steel enclosures available (for 32 zone XFP panels only)
|
ZFP 1 - 2 LOOP ADDRESSABLE CONTROL PANEL
- Comply with European Standard EN54 parts 2 and 4.
- Attractive 450 x 462 x 127mm cabinet.
- Up to 64 eight-loop peer to peer panel network capacity.
- Hi-integrity and single-path networking options. Ability to assign individual zones across the network.
- Very flexible cause and effects.
- Wide range of Switch & Indicator modules.
- Multiple 'A-Bus' expansion PCBs (I/O Units, Relays, etc).
- User-friendly full colour touchscreen with dynamic buttons and virtual QWERTY keyboard.
- 40 separate and programmable zonal LEDs.
- Up to 38 characters of custom text per loop device.
- Automatic daylight saving (BST/GMT) mode.
- 20,000+ event memory (filterable by fire, fault & date).
- Non-fire supervisory event functionality.
- Built-in Thermal Printer.
- Well-designed cabinets with easily removable electronics chassis.
- 20-way heavy-duty brass earth bar as standard.
- 72-hour standby (+ 30 min alarm) in standard cabinets.
- Built-in loop status & current-reading.
- Powerful engineering and commissioning functions including SafeMode and DeviceManager.
- Attractive Compact Controllers.
- Wide range of flush-fit bezels
- Powerful and intuitive PC programming tools
|
ZFP 2 ~ 8 LOOP ADDRESSABLE CONTROL PANEL  - Third-party certified to EN54 parts 2 and 4 by lntertek
- Communication protocal – Apollo XP95/Discovery
- Full compactibility with the Context Plus range of fire detectors, call points, sounders, becons and control modules.
- Three cabinet sizes – standard (1,2 or 4 loops), medium (2,4,6 or 8 loops) and large (2,4,6 or 8 loops)
- Full colour LCD touchscreen with an intuitive interface & digital QWERTY keyboard (touchscreen can be fully customised with a company logo)
- Secure fault tolerant network (needs separate network driver PCB) Up to 128 peer to peer node capacity (64 panels plus up to 64 Compact Controllers/Repeaters
- Very flexible cause and effects
- Wide range of Switch & Indicator modules c/w slide-in lables for straightforward customisation.(Common word processor templates available online)
- Multiple “A-Bus” peripherals (1/0 Units, Relays, Sounder Extender Cards, Conventional Zone Cards, etc)
- Programmable via galvanically isolated USB port
- Up to 200 separate zonal LEDs per panel (100 on standard sized cabinets).
- 10,000 programmable and inficatable detection zones. Up to 38 characters of custom text per loop device.
- Wide range of supported languages.
- Emailable firmware updates (no flash programmer required) 20,000+ event memory (filterable by fire, fault and date) Automatic daylight saving (BST/GMT)
- 4 programmable operational modes.
- Optional thermal printer with front-loading paper. PC logging option for end-user.
- 4 GB Micro SD memory simplifies off-site configuration. Well-designed metal cabinets aid installation.
- 20-way heavy duty brass earth bar(s) as standard
- 72-hour standby (plus 30 min alarm) in standard cabinets. Powerful engineering and commisioning functions including ‘SafeMode’, ‘DeviceManager’ and more.
- Powerful and intuitive PC programming tools. Optional graphical interface solutions.
- Up to 18Ah batteries in standard cabinets, 38Ah in larger cabinets.
|
ANNUNCIATOR REPEATER PANEL FOR ZFP SERIES
- The Context Plus ZREP1S is an intelligent addressable ZFP network device that can be used as a traditional but compact repeater panel with added functionality.
- Includes a Z41 Touchscreen Control Module and ZHN ‘Hi-Net’ multi-path fault-tolerant network PCB.
- Housed in a stylish surface mounting plastic enclosure measuring just 214mm x 178mm x 70mm.
- Can be used to an enhance a building’s reception area and access points (locate your main ZFP panels out of sight and let our ZFP Compact Controllers add a touch of class to your surroundings).
- Full Access Level 2 functionality (silence, disable, reset, etc).
- Requires a separate EN54-4 boxed PSU such as our BF360-24 1A 24V boxed PSU.
- Up to 64 Compact Controllers can be connected to a ZFP network (each controller classed as 1 network node)
|
OPTICAL SMOKE DETECTOR (MODEL 55000-600IMC)
The Optical Smoke Detector has a moulded extinguishing white polycarbonate case with wind resistant smoke inlets and is distinguished by the indicator LED which is clear in standby and red in alarm. Within the case is printed circuit board which, on one side has the light proof labyrinth chamber with integral gauze surrounding the optical measuring system and on the other, the address capture, signal processing and communications electronics.An infrared light emitting diode within its collimator is arranged at an obtuse angle to the photo-diode. The photo-diode has an integral daylight blocking filter.
- Supply voltage from 17 to 28 Volts DC
- Quiescent current at 340µA average, 600µA peak surge current at 1mA
- Two wire supply of polarity insensitive
- Operating temperature range from -20°C to +60°C
- Clear LED emitting red light as alarm indicator
- Sensitivity to nominal threshold of 2.4% light grey smoke obscuration per meter
- 0% to 95% relative humidity with no condensation or icing
- IP rating of 43
- 100mm (Diameter) x 42mm (Height)
- 105g
|
HIGHT TEMPERATURE HEAT DETECTOR (MODEL 55000-400IMC)
The Context Plus Intelligent Addressable High Temperature Heat Detector model 55000-401IMC monitors temperature by using a single thermistor which provides a count output proportional to the external air temperature. This heat detector is classified as an CS device and will report an alarm at 90°C.
- Supply voltage from 17 to 28 Volts DC
- Quiescent current at 250µA average, 500µA peak, surge current at 1mA
- Two wire supply of polarity insensitive
- Operating temperature range from -20°C to +70°C
- Red light emitting diode (LED) as alarm indicator
- Sensitivity range from 25°C to 90°C ( 1°C/Count; -20°C returns to 8 counts)
- 0% to 95% relative humidity with no condensation or icing
- IP rating of 53
- 100mm (Diameter) x 42mm (Height)
- 105g
|
ZONE MONITOR MODULE (MODEL 55000-8415IMC)
 The Zone Monitor powers and controls a zone of up to 20 Series 65 conventional fire detectors from a loop of DEMCO’s addressable detectors and interfaces.The Zone Monitor is loop powered and operates at 17–28V DC with protocol pulses of 5–9V. It is supplied with a backbox for surface mounting, and is also available without the backbox for flush mounting. Both versions are for indoor use only. Two LEDs, one red and one yellow, are visible through the front of the enclosure. The red LED indicates that a fire condition has been detected on the zone wiring. The yellow LED is lit when the built-in isolator has sensed a short circuit loop fault.
- Loop powered and operates at 17–28V DC.
- Supplied with a backbox for surface mounting.
- Fitted with a bi-directional short-circuit isolator.
- For indoor use only.
- Specification:
Zone Voltage (loop voltage ?22V) | 19V±1V | Zone voltage (loop voltage <22V | Loop voltage -1.5V | Switch-on surge, max 150ms | 3.5mA | Quiescent | 4mA + detector load | Operating Temperature | –20°C to +70°C | Humidity (no condensation) | 0–95% RH | IP rating | 54 | Dimensions of Zone Monitor Unit (surface mount) | 150 x 90 x 48 mm | Weight | 230g |
|
SOUNDER CONTROLLER MODULE (MODEL 55000-852IMC)
The Sounder Control Unit (55000-8521IMC) is used to control the operation of a zone of externally powered conventional sounders and VADs to report their status to a DEMCO’s fire alarm control panel.
- Allow sounders to be operated continuously or pulsed.
- Opto-coupled input is provided to monitor the state of the external PSU.
- Fitted with a bi-directional short-circuit isolator.
- Monitor the presence and polarity of the external PSU.
- Supplied with a backbox for surface mounting.
- Specification:
Min Loop in Operating Voltage | 17V DC | Max Loop Operating Voltage | 28V DC | Switch-On Surge, Max. 10ms | 2.6mA | Quiescent | 1.95mA | Operating Temperature | –20°C to +70°C | Humidity (no condensation) | 0–95% RH | IP rating | 54 | Dimensions of Sounder Control Unit (surface mount) | 150 x 90 x 48 mm | Weight | 240g |
|
INPUT/OUTPUT MODULE (MODEL 55000-847IMC)
The Input/Output Unit provides supervision of one or more normally open contacts connected to a single pair of cables and a set of change-over relay output contacts.Compliant with EN54-17 & 18, it is set to return an analogue value of 4 in the event of an open or short-circuit fault and 16 during normal operation. The status of the inputs is reported by means of two input bits. The change-over contacts are operated by an output bit. It is fitted with a bi-directional short-circuit isolator and will be unaffected by loop short circuits on either loop input or output. - Supervision of one or more normally open contacts
- Compliant with EN54-17 & 18
- Fitted with a bi-directional short-circuit isolator
- Specification:
Min Loop in Operating Voltage | 17V DC | Max Loop Operating Voltage | 35V DC | Power-Up Surge Current | 900uA | Quiescent | 500uA | Maximum Cable Resistance | 50 Ohm | Maximum Continuous Current | 1A | Operating Temperature | –40°C to +70°C | Humidity (no condensation) | 0–95% RH | IP rating | 54 | Dimensions of Input/Output Unit (surface mount) | 60 x 150 x 90mm | Weight | 244g |
|
SWITCH MONITOR MODULE (MODEL 55000-847IMC)
The Context Plus Intelligent Addressable Switch Monitor is designed to monitor the state of one or more single pole, volt-free contacts connected on a single pair of cables to report the status. It has a selectable status reporting delay making it suitable for monitoring flow switches
The Intelligent Switch Monitor is available in the new faceplate style enclosure. This can be mounted with the supplied back-box for surface mounting or flush mounted using a UK double gang, flush mounting back-box of minimum depth 30mm. - Improved design for ease of wiring meaning faster installation
- Incorporates a short circuit isolator
- Five pre-configured modes
- Priority mode for fast response
- Configurable input styles
- Earth fault monitoring
- Specification:
- Minimum loop operating voltage in normal
conditions: 17V DC
- Maximum loop operating voltage: 35V DC
- Maximum current consumption at 24V:
- Power surge up current: 900uA
- Quiescent: 500uA
- LEDs off: 500uA
LEDs on: 2mA Max
- Maximum continuous current: 1A
- Maximum cable resistance: 50Ω
- Operating temperature: –40°C to +70°C
- Humidity (no condensation): 0–95%RH
- Shock, vibration and impact: to EN54-17
to EN54-18
- IP rating: 54
- Radiated and conducted RF emissions to:
BS EN50081-1 & 2
- Radiated and conducted RF immunity to:
BS EN50130-4
- Dimensions of switch Monitor (surface mount):
60x 150 x 90mm
- Weight: 239g
- Warranty: 10 Years
- Compliant with EN54-17 and EN45-18
|
ADDRESSABLE MANUAL CALL POINT (MODEL SA5900-908IMC)
The Intelligent Manual Call Point is intended for indoor applications. An alarm is initiated by pressing its glass element. This device signals its status to the fire alarm control panel using an interrupt feature within the system’s digital protocol.An alarm status is indicated on the call point through a solid red LED. The manual call point can be easily test using the supplied test key. The address of the call point is set by a DIL switch.
- Operating Voltage from 17 to 30 Volts DC
- Operating temperature range from -10°C to +50°C
- Addressable number range from 1 to 126
- Alarm current at 13mA
- 0 to 95% RH humidity with no condensation
- IP rating of 24D
|
Addressable loop powered combined Sounder/Beacon with Voice Alarm, Weatherproof, Deep Base IP33C, Hi-Output, Red -EN54-3 compliantThe Context Plus Addressable loop powered combined Sounder/Beacon with Voice Alarm has Superb sound intelligibility. • Includes three selectable voice message pairs. • Provides ‘W-2.4-8.2’ light distribution when wall mounted (min 0.4 lux over a 2.4m x 8.2m cuboid area using the same lens and electronics as our EN54-23, 3 & 17 certified wall sounder VAD). • Onboard short-circuit loop isolator. • 550µA quiescent current. • 19.5mA alarm current @24V DC (VAD lit, voice sounder on max). • Group addressing facility allows multiple devices to be operated simultaneously. • 7 selectable volume levels and up to 15 selectable tone pairs. • IP33C (Type B) rated. |
|